5.0 SYSTEM DIAGNOSTICS
5-24
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
5.8
DIAGNOSTIC MENU 5
From the Diagnostic Menu 4 screen, press the F6 button to view the Diagnostic Menu 5 screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
D I A G N O S T I C M E N U 5
B
F 1 - P A G E S F 4 - F A A S T
C
F 2 - A U D P R I F 5 -
D
F 3 - M S G I D F 6 - M E N U 1
Exhibit 5-32: Diagnostic Menu 5
Press the corresponding function button to display the selected diagnostic screen:
F1
= Page Status
F2
= Audio Priority Status
F3
= Play Message ID Status
F4
= FAAST Detector Status
F5
= Not Used
F6
= Menu 1
5.8.1
PAGE STATUS
The Page Status screen allows you to view the general “paging” status of the panel. There are no selectable
items on this screen. From the Diagnostic Menu 5 screen, press the F1 button to view the Page Status
screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A L E R T T O P A G E : O F F
B
E V A C T O P A G E : O F F
C
D
Exhibit 5-33: Page Status Screen
•
Row A – When a Page-to-Alert switch is pressed and zones that were in Alert are now in page
mode, this line shows “ALERT TO PAGE: ON”; otherwise, “ALERT TO PAGE: OFF” is displayed.
•
Row B – When a Page-to-Evac switch is pressed and zones that were in EVAC are now in page
mode, this line shows “EVAC TO PAGE: ON”; otherwise, “EVAC TO PAGE: OFF” is displayed.