1.0 INTRODUCTION
1-20
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Exhibit 1-18: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(FAAST
Detector)
Day Sensitivity Levels
Fire 1
Y
Range 1-H
(0.00046%ft – 0.04980%ft)
Range 2-M
(0.05%ft – 0.09982%ft)
Range 3-M
(0.1%ft – 0.99645%ft)
Range 4-L, 2.5%
(1%ft – 3.98818%ft)
Copy from Night Sensitivity
Y
Yes /
No
Night Sensitivity
Fire 1
Y
Range 1-H
(0.00046%ft – 0.04980%ft)
Range 2-M
(0.05%ft – 0.09982%ft)
Range 3-M
(0.1%ft – 0.99645%ft)
Range 4-L
(1%ft – 3.98818%ft)
Copy from Day Sensitivity
Y
Yes /
No
Miscellaneous
Particulate Level Display
Y
Fire 2 /
Fire 1
/ Action 2 /
Action 1 / Alert
Air Flow Trouble Boundary
Y
0 – 100 (% off normal)
(20% default)
Air Flow Trouble Timer
Y
No Timer
/ Timer 1 / Timer 2 /
Timer 3
Security
Test Button/Functions Locked
Y
Enabled
/ Disabled
Isolate Button/LCD Settings
Locked
Y
Enabled
/ Disabled
Configuration Locked
Y
Enabled
/ Disabled
Can be Disabled
Y
Enabled /
Disabled
Passcode
Y
0 – 9999
(1111 default)
Device Disable (Isolate Button)
Y
Enabled /
Disabled
Reference Detector
Analog Broadcast Increasing Step
Y
0 -
255
1
Analog Broadcast Decreasing
Step
Y
0 -
255
1
Reference Detector Address
Y
0
- 254
2
Relays
Configuration (Relays 1 – 5)
Y
Latching: Yes /
No
Y
Fire 2 /
Fire 1
/ Action 2 /
Action 1 / Alert
Configuration (Relay 6)
Y
Latching: Yes /
No
Y
High Airflow / Low Airflow /
Isolate / Filter Minor / Filter
Urgent / Filter Door / Config /
Aspirator / Low Voltage /
Comm / Time / Sensor
Notes:
1.
Set to 255 to disable Analog Broadcast.
2.
Reference detector cannot use Acclimate feature.