1.0 INTRODUCTION
1-32
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Exhibit 1-30: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Smoke
Control
Graphic Card
6-Zone
Smoke Group Configuration
Group
Y
1
- 6
Switch Group Configuration
Y
On / Off / Auto
Switch Function
Y
No Function Assigned
/
Smoke Control
Select Relay Actions
(when switch is pressed)
Y
None
/ On / Auto / Off
1,2
Action Start
Y
Action starts with
confirmation address OR
delay timer / Action starts
with confirmation address
AND delay timer
Confirmation Address
Y
Loop:
0
– 4
Address:
0
- 254
Relay Address
Y
Panel:
0
- 128
Loop:
0
- 4
Address:
0
- 254
Delay (relay activation)
Y
0
– 255 seconds
Delay Timer Start
Y
Delay timer starts
immediately / Delay timer
starts after confirmation
address activates
LED Configuration
Y
On / Off / Auto / Fault
Notes:
1.
On and Off overrides up to 25 addressable relays on the panel’s SLCs.
2.
Auto returns up to 25 addressable relays back to automatic configured state.