6.0 SYSTEM MAINTENANCE
6-6
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Once the source device loop/address has been selected and the ENTER button has been pressed, the panel
will read the configuration from the selected device and store it in the panel. Retrieval of the configuration can
take several seconds. Do not press any buttons or navigate away from this screen while the “Retrieving
Config From Device” message is displayed. Doing so may cause loss of configuration data. The following
screen will not be displayed if the panel memory already holds a configuration for the device:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
R E T R I E V I N G C O N F I G
B
F R O M D E V I C E
C
> > > > > > > > > > > > > > > <
D
P L E A S E W A I T
Exhibit 6-10: Retrieving Configuration Screen
The panel will then prompt you to replace the device and press the ENTER button to proceed:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
R E P L A C E D E V I C E O N
B
A D D R E S S A B L E L O O P
C
P R E S S E N T E R
D
W H E N C O M P L E T E
Exhibit 6-11: Device Replace Screen
The panel will send the device configuration stored in the panel to the new device. The serial number stored
in the panel for the replaced device will be replaced with the serial number from the new device. The
following screen will be displayed to show that the process is proceeding:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
C O N F I G U R I N G
B
N E W D E V I C E
C
> > > > > > > > > > > > > > < <
D
P L E A S E W A I T
Exhibit 6-12: Device Configuration Screen
•
Row D - Displays COMPLETED once the device has been configured.
The panel will record a DEVICE REPLACE OK (or FAIL, if there was a failure) event in the history buffer once
the device replacement process is complete. The following screen will appear automatically to allow
replacement of another device:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
R E P L A C E
S U C C E E D E D
B
L O O P : 1 A D D R E S S : 0 0 1
C
T Y P E : P H O T O S E N S O R
D
E N T E R F O R N E X T D E V I C
Exhibit 6-13: Device Replace Success Screen
The panel will perform a reset and log a CONFIG CHANGE TIMEOUT record at the conclusion of the device
replacement if there is no button entry within 100 seconds.