6.0 SYSTEM MAINTENANCE
UL S2203
CyberCat 254/1016 Operation Manual
6-3
FM
P/N: 06-326-2
Rev 6, 09/2015
6.4 PANEL MAINTENANCE MENUS
The CyberCat’s Maintenance Menu provides several features that can be used by service personnel to
maintain and test the addressable devices connected to the panel’s SLC circuits. It is intended for those who
are trained and authorized to service Fike systems. Certain functions of the maintenance menus are
password protected to prevent unauthorized access. To gain access to the password protected functions,
you must enter a valid Level 2 or 3 password. See Section 2.2.1 for instructions on how to log onto the
system. Entering a Level 2 password restricts the maintenance menu options that you are able to use (as
noted).
6.4.1
MAINTENANCE MENU 1
From the Top Level Menu, press the F5 button to access the Maintenance menu:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
M A I N T E N A N C E M E N U
B
F 1 - D E V R D F 4 - W A L K T S
C
F 2 - D E V A D R F 5 - B U Z Z E R
D
F 3 - D E V R P L F 6 - M E N U 2
Exhibit 6-3: Maintenance Menu
Press the corresponding function button to display the selected maintenance screen:
F1
= Read device loop/address
F2
= Assign loop/address to device
F3
= Replace device sequence
F4
= Select Walktest mode
F5
= Disable on-board buzzer
F6
= Maintenance Menu 2
6.4.1.1
DEVICE READ
The Device Read screen allows you to see the address and device type of the most recent device attached to
the loop. From the Maintenance Menu, press the F1 button to access the Device Read screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
M O S T R E C E N T D E V I C E
B
A T T A C H E D T O P A N E L
C
L O O P : 1 A D D R E S S : N N N
D
T Y P E : D E V I C E T Y P E
Exhibit 6-4: Device Read Screen
•
Row C - Displays the ADDRESS of the most recent device attached to the loop. To read a
device address, either add it to the loop while this screen is displayed, or temporarily remove and
replace the device for panel to read the address.
•
Row D - Displays the device type of the most recently identified address in Row C.
Note:
Pressing the ENTER button will clear the loop and address to zeroes and the type message to
blanks.
Note:
If at any time during a DEVICE READ there is a communication error between the panel and the
device the panel will display “DEVICE COMM ISSUES” then a re-read of the device MUST be performed.