1.0 INTRODUCTION
1-34
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Exhibit 1-32: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Smoke
Control
Graphic Card
6-Zone
Miscellaneous
Peripheral Address
Y
2 – 32
Local Buzzer
Y
Enabled
/ Disabled
Graphic Switch Configuration
(CFG1 and CFG2)
Y
No Function Assigned
/
Reset / Silence /
Acknowledge / Drill / LED
Test
Graphic LED Configuration
(CFG1 thru CFG3)
Y
No Function Assigned / Panel
Silence / Panel Drill / Panel
Walktest / Panel Comm OK /
Panel Power OK
Voice EVAC
Switch Card
Peripheral Address
Y
2 - 32
Priority Level
Y
0 – 254
Default 1
Copy EVAC Zones to Alert and
Page
Y
Yes /
No
Voice Evac Switch Groups 1 - 6
EVAC Switch
Y
Enabled /
Disabled
EVAC Zone Assignments
Y
1
– 254
ALERT Switch
Y
Enabled /
Disabled
ALERT Zone Assignments
Y
1
– 254
PAGE Switch
Y
Enabled /
Disabled
PAGE Zone Assignments
Y
1
– 254
Fire Phone
Card
Peripheral Address
Y
2 - 32
SLC Wiring Class
Y
Class A /
Class B
Device Address
Y
1 – 99
1
Notes:
1.
Select only the fire-phone module addresses that are connected to the fire-phone riser.