6.0 SYSTEM MAINTENANCE
6-10
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
6.4.2
MAINTENANCE MENU 2
From the Maintenance Menu 1 screen, press the F6 button to access the Maintenance Menu 2 screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
M A I N T E N A N C E M E N U 2
B
F 1 - M N S R S T F 4 - C F G R D
C
F 2 - M N S S I L F 5 - F A A S T
D
F 3 -
S W T I M E
F 6 - A H U O N
Exhibit 6-17: Maintenance Menu 2
Press the corresponding function button to initiate the selected function or display the selected maintenance
screen:
F1
= Mass Notification System Reset
F2
= Mass Notification System Silence
F3
= Switch Timeout (
blank unless panel is configured for City of Chicago Operation
)
F4
= Device Configuration Read
F5
= FAAST
F6
= AHU On
6.4.2.1
MASS NOTIFICATION SYSTEM RESET
When the voice system amplifiers are activated for mass notification (MNS), they cannot be reset using the
standard control panel reset switches. The MNS Reset function provides a means for the system operator to
reset the MNS system from the control panel (local or network). Resetting the MNS system does not impact
the operation of any active Fire Alarm inputs or outputs.
From the Maintenance Menu 2 screen, press the F1 button to reset the mass notification system.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
M A I N T E N A N C E M E N U 2
B
F 1 - * * * * * * * F 4 - C F G R D
C
F 2 - M N S S I L F 5 - F A A S T
D
F 3 -
S W T I M E
F 6 - A H U O N
Exhibit 6-18: MNS Reset Screen
•
Row B - Once F1 is pressed, the display will show “*******” for about one second. Any amplifiers
activated for MNS operation and active MNS switches will return to normal operation. The MNS
contact on the FCC digital paging card will deactivate unless configured for latching operation. A
system administrator level password is required for this switch to function.