1.0 INTRODUCTION
UL S2203
CyberCat 254/1016 Operation Manual
1-21
FM
P/N: 06-326-2
Rev 6, 09/2015
Exhibit 1-19: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(FAAST
Detector)
FAAST XT
Enable Channels
Y
1 - 4
Fan Speed
Y
Slow /
Medium
/ Fast
Alarm Sounder
Y
Off
/ Pulsed / Continuous
Fault Sounder
Y
Off
/ Pulsed / Continuous
Defaults
(Dual
Monitor
Module)
Loop Number of Device
Y
1
- 4
1
Address of Device
Y
1
– 254
Custom Message
Y
60 character user defined
(1-001 INPUT ALM/SUP
Loop 1 - Address 001)
Y
Default /
User Defined
Zone Assignments
Y
1
– 254
2
Input 1 Function
Y
No Input Function
/
Manual
Alarm
/ Detection/ Waterflow
/Pre-Alarm 1 / Pre-Alarm 2 /
Supervisory / Trouble /
Process / PAS Inhibit / Reset
/ Silence / Acknowledge / Drill
/ Fan Restart
Y
Latching
/ Non-Latching
3
Y
Normally Open
/ Normally
Closed
4
Y
Short Detection On
/
Short
Detection Off
Input 2 Function
Y
No Input Function
/ Pre-Alarm
1 / Pre-Alarm 2 /
Supervisory
/ Trouble /
Process / AHU FD Key
Y
Latching
/ Non-Latching
3
Y
Normally Open
/ Normally
Closed
4
Y
Short Detection On
/
Short
Detection Off
Notes:
1.
CyberCat 254 has only one (1) addressable loop. CyberCat 1016 can have up to four (4) addressable loops.
2.
Can be assigned to 4 discrete zones, 2 zone ranges or 1 range and 2 discrete zones.
3.
Either = PA1, PA2, Supervisory, Trouble, Process, PAS Inhibit; Non-Latch = Reset, Silence, Acknowledge, Zone Disable, Fan
Restart; Latching = ManAlarm, Detection, Waterflow, Drill.
4.
NO Contacts = Detection, Manual Alarm, Reset, Supervisory; NO/NC Contacts = Process, Waterflow, PA1, PA2, Trouble, Drill,
Silence, Acknowledge, Zone Disable, PAS Inhibit, Fan Restart.