5.0 SYSTEM DIAGNOSTICS
UL S2203
CyberCat 254/1016 Operation Manual
5-21
FM
P/N: 06-326-2
Rev 6, 09/2015
5.7.3
VOICE ZONES
The Voice Zones screen allows you to view the status of system zones with respect to voice conditions. From
the Diagnostic Menu 4 screen, press the F3 button to view the Voice Zones screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
Z O N E R A N G E : 0 0 1 - 0 2 0
B
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
C
- - - - - - - - - - - - - - - - - - - -
D
Z : 0 0 1 S T A T : A U T 0 - N O N E
Exhibit 5-28: Voice Zones Screen
•
Row A - Allows you to select the range of zones in groups of 20 that will be displayed in Row C.
Use the +/- buttons to increment or decrement the zone range.
•
Row B – These numbers act as placeholders for the range of zones selected in Row A.
•
Row C – Displays a single letter description of the voice condition for the zone that aligns with the
zone number on Row B.
-
= No voice condition is active
C
= Zone is in “Automatic” operation and Process is the highest voice priority state in that zone.
S
= Zone is in “Automatic” operation and Supervisory is the highest voice priority state in that zone.
T
= Zone is in “Automatic” operation and Test Alarm (walk-test mode) is active in that zone.
L
= Zone is in “Automatic” operation and Alarm is the highest voice priority state in that zone.
A
= Zone is in “Alert” condition. Use line 4 to determine if this is from “Automatic” or a manual switch.
E
= Zone is in “Evacuate” condition. Use line 4 to determine if this is from “Automatic” or a manual
switch.
D
= Zone is in “Drill” condition. The drill switch has been pressed.
P
= Zone is in “Page” condition. A page switch for this zone has been pressed.
R
= Zone is in “Page with Record and Repeat” condition. A page with record and repeat switch for this
zone has been pressed.
F
= Zone is in “Play Fire Message” condition. A play fire message switch for this zone has been
pressed.
M
= Zone is in “Play Mass Notify Message” condition. A play MNS message switch for this zone has
been pressed.
G
= Zone is in “”Page” condition. A page switch for this zone has been pressed.
O
= Zone is in “Page with R&R” condition. A page with R&R switch for this zone has been pressed.
Use the
◄► arrow keys to scroll through the 254 available zones.
•
Row D (Z:) – Displays the zone number at the cursor position.
•
Row D (STAT:) – Displays the status of the zone as:
“AUTO-NONE”
– No voice condition is active in this zone.
“AUTO-PROC”
– Zone is in “Automatic” operation with Process state active.
“AUTO-SUPV”
– Zone is in “Automatic” operation with Supervisory state active.
“AUTO-TEST”
– Zone is in “Automatic” operation with Test Alarm state active.
“AUTO-ALRM”
– Zone is in “Automatic” operation with Alarm state active.
“AUTO-ALRT”
– Zone is in “Automatic” operation with Alert condition active.
“AUTO-EVAC”
– Zone is in “Automatic” operation with Evacuate condition active.
“DRILL”
– Zone is in Drill condition.
“ALERT”
– Zone is in Alert condition via a manual switch.
“EVACUATE”
– Zone is in Evacuate condition via a manual switch.
“PAGE”
– Zone is in Page condition.
“PAGE W RR”
– Zone is in Page with record and repeat condition.
“FIRE MSG”
– Zone is in Play Fire Message condition.
“MNS MESSG”
– Zone is in Play MNS Message condition.
“MNS PAGE
” – Zone is in MNS PAGE condition.
“MNS W R&R”
– Zone is in MNW PAGE WITH RECORD AND REPEAT condition.