4.0 SYSTEM HISTORY
UL S2203
CyberCat 254/1016 Operation Manual
4-3
FM
P/N: 06-326-2
Rev 6, 09/2015
4.2.1 ALARM HISTORY
The ALARM History screen allows you to view the current alarm events (1,600 total) present on the system
since the last Reset of the panel. From the History Menu, press the F1 button to display the Alarm History
screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A A L A R M : D E V I C E T Y P E
B C U S T O M M E S S A G E X - X X X
C 1 2 : 2 4 : 4 4 P
0 2 / 0 5 / 2 0 0 9
D E V E N T 0 0 1 O F 0 0 0 1
Exhibit 4-5: Alarm History Screen
•
Row A - Displays the type of device in Alarm.
•
Row B - Displays the custom message of the device in Alarm. Press the F1 button to
further locate event.
•
Row C - Displays the time and date that the Alarm event was initiated.
•
Row D - Displays the Alarm event number in the order received and the total number of
current Alarm events present on the system.
Use the
+/–
buttons on the display to scroll through all Alarm events in the history buffer.
4.2.2 SUPERVISORY HISTORY
The SUPERVISORY History screen allows you to view the current supervisory events (800 total) present on
the system since the last Reset of the panel. From the History Menu, press the F2 button to display the
Supervisory History screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S U P E R V I S O R Y I N P U T
B C U S T O M M E S S A G E X - X X X
C 1 2 : 2 4 : 4 4 P
0 2 / 0 5 / 2 0 0 7
D E V E N T 0 0 1 O F 0 0 0 1
Exhibit 4-6: Supervisory History Screen
•
Row A - Displays a description of the Supervisory event.
•
Row B - Displays the custom message of the Supervisory event.
•
Row C - Displays the time and date that the Supervisory event was initiated.
•
Row D - Displays the Supervisory event number in the order received and the total
number of current Supervisory events present on the system.
Use the
+/–
buttons on the display to scroll through all Supervisory events in the history buffer.