5.0 SYSTEM DIAGNOSTICS
5-18
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
5.7.2
PERIPHERAL SUPERVISION DATA
The Peripheral Supervision Data screen allows you to view the analog-to-digital conversion values for the
peripheral device selected on Row A. From the Diagnostic Menu 4 screen, press the F2 button to view the
Peripheral Supervision Data screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A M P A T : 0 2 G # # K # # O #
B
A # # # D # # # H # # L # # P #
C
B # # # E # # # I # # M # # Q #
D
C # # # F # # # J # # N # # R #
Exhibit 5-27: Peripheral Supervision Data Screen
Note:
At present, only the amplifier card (AMP), digital paging module (DPM) and remote paging card
(MIC) will display supervision data on this screen.
•
Row A (1 through 9) - Displays the device type and peripheral address of the selected device.
•
Rows A-D (A through R) - Displays the current supervision data of the selected peripheral device.
If there is not a device configured for the selected peripheral address or if the device is not an
amplifier, digital paging module or remote paging card, the screen will display “NO DATA”. A
description of each data field for each peripheral device type is provided below:
1. Amplifier Card Values
A### - Message ID1 (Fire message = 1-16, MNS message = 101-116, MNS Page = 251, MNS
R&R = 252, Fire Page = 253, Fire R&R = 254)
B### - Message ID2 (Fire message = 1-16, MNS message = 101-116, MNS Page = 251, MNS
R&R = 252, Fire Page = 253, Fire R&R = 254)
C### - Active speaker circuit and audio source (See table below for description of values).
D### - Audio bus troubleshooting (Increments periodically if the amplifier does not receive any
valid packets on the audio bus. Once the counter reaches max value of 255, it stays at 255 until
the fault clears. Once the amp starts receiving valid packets, the counter is decremented
periodically.
E### - A-D value (0 – 255) for power-limited supervision on speaker circuit. Threshold for short
on a 25 V amp >= 216 (~2.79 V), threshold for short on a 70 V amp >= 120 (~1.55 V).
F### - Amplifier input voltage configuration (120 V = 0, 240 V = 1)
G## - Amplifier output voltage configuration (25 V = 25, 70 V = 70)
H## - Manual activation state (Automatic Operation = 0, Drill = 1, Alert = 2, Evac = 3, Page = 4)
I## - Automatic activation state (Normal = 0, Process = 1, Supervisory = 2, Test Alarm = 3, Alarm
= 4, Alert = 5, Evac = 6)
J## - City Code (Standard = 0, Boston Alarm Active = 1, Chicago = 2, NYC Evac = 3, NYC Inquiry
= 4, NYC Alarm Acknowledge = 5)
K## - NAC circuit active or not active (Not active = 0, Active = 1)
L## - NAC protocol configuration (Constant ON = 0, Gentex = 1, System Sensor = 2, Wheelock =
3)
M## - Contact monitor circuit state (No Active = 0, Active = 1)
N## - Contact monitor configuration (Disabled = 0, Enabled = 1)
O# - Battery charging configuration (Disabled = 0, Enabled = 1)
P# - Local page configuration (Disabled = 0, Enabled = 1)
Q# - Dual-channel mode configuration (Disabled = 0, Enabled = 1)
R# - Audio bus configuration (Disabled = 0, Enabled = 1)