3.0 SYSTEM OPERATION
UL S2203
CyberCat 254/1016 Operation Manual
3-7
FM
P/N: 06-326-2
Rev 6, 09/2015
3.3.3
ALARM / WATERFLOW STATE
When and initiating device (detector, manual pull and input configured for detection or waterflow) activates,
the control panel does the following:
1. ALARM LED flashes.
2. Panel sounder pulses.
3. LED on active device will turn on (RED) to indicate its activated status. It will light its remote LED as
programmed, if connected.
4. System Alarm relay (P2) activates.
5. Associated system outputs (notification and control) activate if programmed for specific Zone and
State of activated device.
6. Sends Alarm message to remote displays, history buffer, printers, and PC monitoring stations, DACT
7. Displays Alarm event on the LCD display as follows:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A L A R M : D E V I C E T Y P E
B
C U S T O M M E S S A G E L - A D R
C
H H : M M : S S A M M / D D / Y Y Y Y
D
E V E N T X X X X O F Y Y Y Y
Exhibit 3-4: Alarm Display
•
Row A – Displays the device type associated with the Alarm event (i.e. photo, photo/heat, photo duct,
ionization, pull station, monitor module, mini monitor module, dual monitor module, conventional zone
module)
•
Row B – Displays the 20 character custom message for the device
•
Row C – Displays the Time and Date of Event
•
Row D – Displays the event number (XXXX) and the total number of current events (YYYY)
How to respond to an Alarm / Waterflow Event:
1. Press the ACKNOWLEDGE button to silence the panel sounder only. The panel ALARM LED will
change from flashing to steady. The control panel will send an acknowledge message to remote
displays, history buffer, printers, PC monitoring stations, and DACT.
2. Press the F1 button to toggle Rows A and B on display to show the Panel-Loop-Address of active device.
3. Press the F2 button to toggle Rows C and D on display to show the extra 40 characters of the devices
custom message.
4. Investigate the cause of the Alarm and if a fire is present, follow the buildings emergency evacuation
procedures.
Proceed to next step only if it is determined that the event is a false Alarm.
5. Press the SILENCE button to silence the panel sounder and any activated outputs that are programmed
as silenceable. The panel ALARM LED will change from flashing to steady. The control panel will send a
silence message to remote displays, history buffer, printers, PC monitoring stations, and DACT.
6. Correct the condition causing the false Alarm; then press the system RESET button to clear the event
and return the panel to the Normal State. The control panel will send a SYSTEM NORMAL message to
remote displays, history buffer, printers, PC monitoring stations, and DACT.
Note:
Waterflow events will initiate a 2 second alarm verification time delay in order to prevent activation
of the module in the case of water pressure surges.