6.0 SYSTEM MAINTENANCE
6-2
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
6.3 FUSE REPLACEMENT
The CyberCat controller has five replaceable fuses (standard automotive) as shown in Exhibit 6-1. These fuses
provide over current protection for the controller and are rated as followed:
F1 – Primary AC Power input, 15 Amp (P/N 02-4174)
F2 – Battery Power input, 15 Amp (P/N 02-4174)
F3 – Auxiliary Power circuit #1, 4 Amp (P/N 02-11412)
F4 – Auxiliary Power circuit #2, 4 Amp (P/N 02-11412)
F5 – Auxiliary Power circuit #3, 4 Amp (P/N 02-11412)
F
F
F3
Exhibit 6-1: Controller Fuse Locations
If the Supplemental Power Supply is installed, it is equipped with five replaceable fuses (standard automotive)
as shown in Exhibit 6-2. These fuses provide over current protection for the controller and are rated as
follows:
F1 – Primary AC Power input, 15 Amp (P/N 02-4174)
F2 – Battery Power input, 15 Amp (P/N 02-4174)
F3 – Auxiliary Power circuit #1, 4 Amp (P/N 02-11412)
F4 – Auxiliary Power circuit #2, 4 Amp (P/N 02-11412)
F5 – Auxiliary Power circuit #3, 4 Amp (P/N 02-11412)
Exhibit 6-2: SPS Fuse Locations
P22
P21
AIRFLOW
F5
F4
F2
F1
F3