8. Operating modes
Festo P.BE-CMMP-CO-SW-EN 0708NH
159
Index
6098
h
Name
homing_method
Object code
VAR
Data Type
INT8
Access
rw
PDO Mapping
yes
Units
Value Range
-18, -17, -2, -1, 1, 2, 7, 11, 17, 18, 23, 27, 32, 33, 34, 35
Default Value
17
Value
Direction
Objective
Reference point for zero
-18
positive
Stop
Stop
-17
negative
Stop
Stop
-2
positive
Stop
Zero pulse
-1
negative
Stop
Zero pulse
1
negative
Limit switch
Zero pulse
2
positive
Limit switch
Zero pulse
7
positive
Homing switch
Zero pulse
11
negative
Homing switch
Zero pulse
17
negative
Limit switch
Limit switch
18
positive
Limit switch
Limit switch
23
positive
Homing switch
Homing switch
27
negative
Homing switch
Homing switch
33
negative
Zero pulse
Zero pulse
34
positive
Zero pulse
Zero pulse
35
No travel
Current actual position
The
homing_method
can only be set when the reference travel is not active.
Otherwise, an error message (see chapter 5.5) is returned.
The process of the individual methods is described in detail in chapter 0.