![Festo CMMP Series Скачать руководство пользователя страница 114](http://html1.mh-extra.com/html/festo/cmmp-series/cmmp-series_manual_2283112114.webp)
6. Setting Parameters
114
Festo P.BE-CMMP-CO-SW-EN 0708NH
Bit
Value
Digital input
0
00000001
h
Negative limit switch
1
00000002
h
Positive limit switch
2
00000004
h
Homing switch
3
00000008
h
Interlock – (contoller or final stage activation missing)
16 … 23 00FF0000
h
Reserved
24 … 27 0F000000
h
DIN0 … DIN3
28
10000000
h
DIN8
29
20000000
h
DIN9
Object 60FE
h
: digital_outputs
The digital outputs can be triggered via the object
60FE
h
. To do this, specify in the object
digital_outputs_mask
which of the digital outputs should be actuated. The selected
outputs can then be set as desired via the object
digital_outputs_data
. It should be noted
that a delay of up to 10 ms may occur in triggering the digital outputs. When the outputs
are really set can be determined by reading back the object
60FE
h
.
Index
60FE
h
Name
digital_outputs
Object code
ARRAY
No. of Elements 2
Data Type
UINT32
Sub-index
01
h
Description
digital_outputs_data
Access
rw
PDO Mapping
yes
Units
--
Value Range
--
Default Value
(dependant on the condition of the brake)
Sub-index
02
h
Description
digital_outputs_mask
Access
rw
PDO Mapping
yes
Units
--
Value Range
--
Default Value
00000000
h
Содержание CMMP Series
Страница 2: ......