6. Setting Parameters
Festo P.BE-CMMP-CO-SW-EN 0708NH
109
Object 2022
h
: synchronisation_encoder_selection
The object
synchronisation_encoder_selection
specifies the encoder input that is used as
synchronisation command value. Depending on the operation mode, this corresponds to a
position command value (profile position mode) or a speed command value (profile
velocity mode).
Only X10 can be used as synchronisation input. As a result, the choice is between X10 and
no input. The same input as for the feedback value encoder should not be used as
synchronisation command value.
Index
2022
h
Name
synchronisation_encoder_selection
Object code
VAR
Data Type
INT16
Access
rw
PDO Mapping
no
Units
--
Value Range
-1, 2 (see table)
Default Value
2
Value
Description
-1
no encoder / undefined
2
X10
Object 202F
h
: synchronisation_selector_data
A synchronous command value can be activated via the object
synchronisation_main
.
Bit 0 must be set for the synchronous command value to be calculated at all. Bit 1 makes
it possible to activate the synchronous position only through the start of a position set.
Currently, only 0 can be parameterised, so the synchronous position is always switched
on. Setting bit 8 makes the homing run take place without activation of the synchronous
position, so master and slave can be referenced separately.
Index
202F
h
Name
synchronisation_selector_data
Object code
RECORD
No. of Elements 1