6. Setting Parameters
80
Festo P.BE-CMMP-CO-SW-EN 0708NH
Object 6510
h
_ 38
h
: iit_error_enable
The object
iit_error_enable
determines how the motor controller acts when the I
2
t
limitation occurs. Either it is only shown in the
statusword
, or error E 31-0 is triggered.
Index
6510
h
Name
drive_data
Object code
RECORD
No. of Elements 51
Sub-index
38
h
Description
iit_error_enable
Data Type
UINT16
Access
rw
PDO Mapping
no
Units
--
Value Range
0, 1
Default Value
0
Value
Meaning
0
I
2
t error OFF
(priority WARNING)
(priority WARNING)
1
I
2
t error ON
(Priority CONTROLLER ENABLE OFF )
(Priority CONTROLLER ENABLE OFF )
The error 31-0 is activated through a change of the error reaction. Reactions that lead to
shutting down of the drive are returned as
ON
, all others as
OFF
. When writing with 0, the
error reaction WARNING is set, when writing with 1 the error reaction CONTROLLER
ENABLE OFF. See cchapter 6.18, Error management.
Object 6410
h
_ 10
h
: phase_order
In the phase sequence (
phase_order
), distortions between motor cable and angle
transmitter cable are considered. It can be taken from the parameterisation software.
A zero equals "right", a one "left".
Sub-index
10
h
Description
phase_order
Data Type
INT16
Access
rw
PDO Mapping
yes
Units
--
Value Range
0, 1
Default Value
0