Commissioning
Micropilot NMR84
66
Hauser
8.
2
1
3
A0042773
1
Datum plate
2
RTD
3
Probe position (→ 136)
Go to the
Probe position
parameter and enter the mounting position of the RTD
(measured from the datum plate).
This parameter, in conjunction with the measured level, determines whether the
measured temperature refers to the product or to the gas phase.
Offset for resistance and/or temperature
An offset for the resistance or the temperature can be defined in the following
submenu: Expert → Input/output → Analog IP X4-8.
•
Ohms offset
is added to the measured resistance before the calculation of the
temperature.
•
Temperature offset after conversion
is added to the measured temperature.
R[ ]
Ω
R[ ]
Ω
T
T
1
2
A0029265
1
Ohms offset
2
Temperature offset after conversion