Micropilot NMR84
Diagnostics and troubleshooting
Hauser
81
11
Diagnostics and troubleshooting
11.1 General trouble shooting
11.1.1 General errors
Error
Possible cause
Remedial action
Device does not respond.
Supply voltage not connected.
Connect the correct voltage.
The cables do not contact the
terminals properly.
Ensure electrical contact between the
cable and the terminal.
Values on the display
invisible
The plug of the display cable is not
connected correctly.
Connect the plug correctly.
Display is defective.
Replace display.
Display contrast too low.
Set Setup → Advanced setup → Display
→ Contrast display to a value ≥ 60 %.
"Communication error" is
indicated on the display when
starting the device or
connecting the display
Electromagnetic interference
Check grounding of the device.
Broken display cable or display plug.
Exchange display.
CDI communication does not
work.
Wrong setting of the COM port on
the computer.
Check the setting of the COM port on
the computer (e.g. FieldCare) and
change it if necessary.
Device measures incorrectly.
Parametrization error
Check and adjust parameterization.
Содержание Micropilot NMR84
Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...
Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...
Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...
Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...
Страница 255: ......
Страница 256: ...www addresses endress com 71545626 71545626 ...