Operating menu
Micropilot NMR84
174
Hauser
"Application" submenu
Navigation
Setup → Advanced setup → Application
"Tank configuration" submenu
Navigation
Setup → Advanced setup → Application → Tank config
"Level" submenu
Navigation
Setup → Advanced setup → Application → Tank config → Level
Empty
Navigation
Setup → Advanced setup → Application → Tank config → Level → Empty
Description
Distance from reference point to zero position (tank bottom or datum plate).
User entry
0 to 10
000.00 mm
Factory setting
Dependent on the device version
Additional information
Read access
Operator
Write access
Maintenance
The reference point is the lower edge of the device flange.
• After changing the
Empty
Table mode
parameter
(→ 208) is automatically set to
Disable
.
• If
has been changed by more than 20 mm (0.8 in), it is
recommended to delete the dip table.
• The dip table values are not affected by a change of the
Empty
parameter
Tank reference height
Navigation
Setup → Advanced setup → Application → Tank config → Level → Tank ref height
Description
Defines the distance from the dipping reference point to the zero position (tank bottom or
datum plate).
User entry
0 to 10
000.00 mm
Factory setting
Dependent on the device version
Содержание Micropilot NMR84
Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...
Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...
Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...
Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...
Страница 255: ......
Страница 256: ...www addresses endress com 71545626 71545626 ...