Selection
• Distance ok
• Distance unknown
• Distance too small
• Distance too big
• Tank empty
• Manual map
• Factory map
Factory setting
Distance unknown
Additional information
Read access
Operator
Write access
Maintenance
Meaning of the options
•
Distance ok
To be selected if the measured distance matches the actual distance. The device
performs a mapping.
•
Distance unknown
To be selected if the actual distance is unknown. No mapping will be recorded in this
case.
•
Distance too small
To be selected if the measured distance is smaller than the actual distance. The device
searches for the next echo and returns to the
Confirm distance
The distance is recalculated and displayed. The comparison must be repeated until the
displayed distance matches the actual distance. After this, the recording of the map can
be started by selecting
"Distance ok" option
.
•
Distance too big
To be selected if the measured distance exceeds the actual distance. The device adjusts
the signal evaluation and returns to the
Confirm distance
parameter (→ 120). The
distance is recalculated and displayed. The comparison must be repeated until the
displayed distance matches the actual distance. After this, the recording of the map can
be started by selecting
"Distance ok" option
.
•
Tank empty
To be selected if the tank is completely empty. The device records a mapping covering
the complete measuring range as defined by the
Empty
parameter (→ 119).
•
Manual map
To be selected if the range of mapping is to be defined manually in the
Mapping end
point
parameter (→ 122). In this case it is not necessary to confirm the distance.
•
Factory map
To be selected if the present mapping curve (if one exists) is to be deleted. The factory
map is used, instead.
When operating via the display module, the measured distance is displayed together
with this parameter for reference purposes.
If the teaching procedure with the
Distance too small
or
Distance too big
option is
quit before the distance has been confirmed, a map is
not
recorded and the teaching
procedure is reset after 60 s.
*
Visibility depends on order options or device settings
5)
Only available for " Evaluation mode (→ 222)" = "Short time history"
Содержание Micropilot NMR84
Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...
Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...
Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...
Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...
Страница 255: ......
Страница 256: ...www addresses endress com 71545626 71545626 ...