Micropilot NMR84
Commissioning
Hauser
73
9.4.11 Configuration of the alarms (limit evaluation)
A limit evaluation can be configured for up to 4 tank variables. The limit evaluation issues
an alarm if the value exceeds an upper limit or falls below a lower limit, respectively. The
limit values can be defined by the user.
A
B
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10
10
A0029539
35
Principle of the limit evaluation
A
Alarm mode = On
B
Alarm mode = Latching
1
HH alarm value
2
H alarm value
3
L alarm value
4
LL alarm value
5
HH alarm
6
H alarm
7
L alarm
8
LL alarm
9
"Clear alarm" = "Yes" or power off-on
10 Hysteresis
The limit evaluation is configured in the
Alarm 1 to 4
submenus.
Navigation path: Setup → Advanced setup → Alarm → Alarm 1 to 4
For
Alarm mode
=
Latching
all alarms remain active until the user selects
Clear
alarm
=
Yes
or the power is switched off and on.
Make sure to also configure the parameter
"Hysteresis" parameter
accordingly,
depending on tank variable and unit used.
Содержание Micropilot NMR84
Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...
Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...
Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...
Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...
Страница 255: ......
Страница 256: ...www addresses endress com 71545626 71545626 ...