Micropilot NMR84
Operating menu
Hauser
185
Additional information
Read access
Operator
Write access
Maintenance
P1 position
Navigation
Setup → Advanced setup → Application → Tank config → Pressure → P1 position
Description
Defines the position of the bottom pressure transmitter (P1), measured from zero position
(tank bottom or datum plate).
User entry
–10
000 to 100
000 mm
Factory setting
5
000 mm
Additional information
Read access
Operator
Write access
Maintenance
P1 offset
Navigation
Setup → Advanced setup → Application → Tank config → Pressure → P1 offset
Description
Offset for the bottom pressure (P1).
The offset is added to the measured pressure prior to any tank calculation.
User entry
–25 to 25 bar
Factory setting
0 bar
Additional information
Read access
Operator
Write access
Maintenance
P1 absolute / gauge
Navigation
Setup → Advanced setup → Application → Tank config → Pressure → P1 absolut/
gauge
Description
Defines whether the connected pressure transmitter measures an absolute or a gauge
pressure.
Selection
• Absolute
• Gauge
Factory setting
Gauge
Содержание Micropilot NMR84
Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...
Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...
Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...
Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...
Страница 255: ......
Страница 256: ...www addresses endress com 71545626 71545626 ...