Micropilot NMR84
Commissioning
Hauser
63
4.
a
A0047111
28
Prothermo NMT8x: Distance between the physical end of the probe and the zero level value
a
Distance between the physical end of the probe and the zero level value in the tank (tank bottom or
datum plate).
To configure a
Prothermo NMT8x
: Go to the
Bottom point
parameter and enter the
distance between the physical end of the probe and the zero level value in the tank
(tank bottom or datum plate).
The value entered into the
Bottom point
parameter in the Tank Gauging device
is handed over to the
End of probe to zero distance
parameter in the connected
Prothermo NMT8x.
To check the temperatures measured by the individual elements, go to the following
submenu: Operation → Temperature → NMT element values → Element temperature
There is a
Element temperature X
parameter for each element of the Prothermo.