Micropilot NMR84
Operating menu
Hauser
175
Additional information
Read access
Operator
Write access
Maintenance
Tank level
Navigation
Setup → Advanced setup → Application → Tank config → Level → Tank level
Description
Shows the distance from the zero position (tank bottom or datum plate) to the product
surface.
Additional information
Read access
Operator
Write access
-
Set level
Navigation
Setup → Advanced setup → Application → Tank config → Level → Set level
Description
If the level measured by the device does not match the actual level obtained by a manual
dip, enter the correct level into this parameter.
User entry
0 to 10
000.00 mm
Factory setting
0 mm
Additional information
Read access
Operator
Write access
Maintenance
The device adjusts the
Empty
parameter (→ 119) according to the entered value, such
that the measured level will match the actual level.
• After the change of the
Empty
Table mode
parameter
(→ 208) is automatically set to
Disable
.
• If
Empty
has been changed by more than 20 mm (0.8 in), it is recommended to
delete the dip table.
• The dip table values are not affected by a change of the
Empty
parameter.
Water level source
Navigation
Setup → Advanced setup → Application → Tank config → Level → Water level src
Description
Defines the source of the bottom water level.
Selection
• Manual value
• Bottom level
• HART device 1 ... 15 level
Содержание Micropilot NMR84
Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...
Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...
Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...
Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...
Страница 255: ......
Страница 256: ...www addresses endress com 71545626 71545626 ...