Lmin
Hr
1
2
A0029148
56
HTMS hysteresis
1
Value calculated
2
Value held/manual
L
min
H
r
Hysteresis (→ 203)
Description of parameters
Navigation
Setup → Advanced setup → Application → Tank calculation
→ HTMS
HTMS mode
Navigation
Setup → Advanced setup → Application → Tank calculation → HTMS → HTMS mode
Description
Defines the HTMS mode. Depending on the mode one or two pressure transmitters are
used.
Selection
• HTMS P1
• HTMS P1+P3
Factory setting
HTMS P1
Additional information
Read access
Operator
Write access
Maintenance
Meaning of the options
• HTMS P1
Only a bottom pressure transmitter (P1) is used.
• HTMS P1+P3
A bottom (P1) and top (P3) pressure transmitter are used. This option should be selected
for pressurized tanks.
Manual density
Navigation
Setup → Advanced setup → Application → Tank calculation → HTMS → Manual
density
Description
Defines the manual density.
Содержание Micropilot NMR84
Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...
Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...
Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...
Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...
Страница 255: ......
Страница 256: ...www addresses endress com 71545626 71545626 ...