Operating menu
Micropilot NMR84
208
Hauser
Description of parameters
Navigation
Setup → Advanced setup → Application → Tank calculation
→ Dip-table
Table settings
Navigation
Setup → Advanced setup → Application → Tank calculation → Dip-table → Table
settings
Description
Defines the dip-table operation to be performed.
Selection
• Manual
• Semiautomatic
• Clear table
• Sort table
Factory setting
Manual
Additional information
Read access
Operator
Write access
Maintenance
Meaning of the options
• Manual
Both, the device level and the dip level for each table point have to be entered manually.
• Semiautomatic
The device level of each table point is measured by the device itself, the corresponding
dip level must be entered manually.
• Clear table
Deletes the complete dip table.
• Sort table
Sorts the table points into an ascending order. This must be performed if table values
have not been entered in the correct order.
Table mode
Navigation
Setup → Advanced setup → Application → Tank calculation → Dip-table → Table
mode
Description
Enables or disables the dip-table.
Selection
• Disable
• Enable
Factory setting
Disable
Содержание Micropilot NMR84
Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...
Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...
Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...
Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...
Страница 255: ......
Страница 256: ...www addresses endress com 71545626 71545626 ...