Micropilot NMR84
Operating menu
Hauser
155
Modbus address
Navigation
Setup → Advanced setup → Communication → Modbus X1-4 → Configuration
→ Device ID
Prerequisite
Communication interface protocol (→ 153)
MODBUS
Description
Defines the Modbus address of the device.
User entry
1 to 247
Factory setting
1
Additional information
Read access
Operator
Write access
Maintenance
Float swap mode
Navigation
Setup → Advanced setup → Communication → Modbus X1-4 → Configuration
→ Float swap mode
Prerequisite
Communication interface protocol (→ 153)
MODBUS
Description
Sets the format of how the floating point value is transferred on Modbus.
Selection
• Normal 3-2-1-0
• Swap 0-1-2-3
• WW Swap 1-0-3-2
Factory setting
Swap 0-1-2-3
Additional information
Read access
Operator
Write access
Maintenance
Bus termination
Navigation
Setup → Advanced setup → Communication → Modbus X1-4 → Configuration → Bus
termination
Prerequisite
Communication interface protocol (→ 153)
MODBUS
Description
Activates or deactivates the bus termination at the device. Should only be activated on the
last device in a loop.
Selection
• Off
• On
Содержание Micropilot NMR84
Страница 177: ...Micropilot NMR84 Operating menu Endress Hauser 177 Additional information Read access Operator Write access Maintenance ...
Страница 204: ...Operating menu Micropilot NMR84 204 Endress Hauser Additional information Read access Operator Write access Maintenance ...
Страница 219: ...Micropilot NMR84 Operating menu Endress Hauser 219 Additional information Read access Operator Write access Maintenance ...
Страница 238: ...Operating menu Micropilot NMR84 238 Endress Hauser Read access Operator Write access Maintenance ...
Страница 255: ......
Страница 256: ...www addresses endress com 71545626 71545626 ...