Commissioning (block-based operation)
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
90
Hauser
12.8.2 Allocation parameters
The allocation of event categories to the event groups is controlled by the allocation
parameters. They reside in the
RESOURCE (RB2)
block:
•
FD_FAIL_MAP
: for the
Failure (F)
event category
•
FD_CHECK_MAP
: for the
Function check (C)
event category
•
FD_OFFSPEC_MAP
: for the
Out of specification (S)
event category
•
FD_MAINT_MAP
: for the
Maintenance required (M)
event category
Each allocation parameter consists of 32 bits with the following meaning:
•
Bit 0:
reserved by the Fieldbus Foundation
•
Bits 1 to 15:
Configurable area; here, a number of predefined diagnostic events can be
allocated irrespective of the group of events they belong to. In this case they are removed
from their group and their bahavior can be configured individually. With Micropilot, the
following parameters can be allocated to the configurable area:
– 941: Echo lost
– 942: In safety distance
– 950: Advanced Diagnostic occurred
•
Bits 16 ... 31:
Standard area; these bits are permanently allocated to a specific group of
events. If a bit is set to
1
, the respective event category is assigned to the group.
The following table represents the default setting of the allocation parameters. In the
default setting there is a unique relationship between the severity of the event and its
category (i.e. its allocation parameter).
Default setting of the allocation parameters
Standard area
Configurable area
Severity of the event
Highest severity
High severity
Low severity
Lowest severity
Source of the event
S
E
C
P
S
E
C
P
S
E
C
P
S
E
C
P
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
15 ... 1
FD_FAIL_MAP
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
FD_CHECK_MAP
0
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
0
FD_OFFSPEC_MAP
0
0
0
0
0
0
0
0
1
1
1
1
0
0
0
0
0
FD_MAINT_MAP
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
0
1)
S: Sensor; E: Electronics; C: Configuration; P: Process
In order to change the diagnostic behavior of a group of events, proceed as follows:
1. Open the allocation parameter to which the group is currently allocated.
2. Switch the bit of the group from
1
to
0
. In the case of operation via FieldCare this is
done by deactivating the respective checkbox (see the example below).
3. Open the allocation to which the group is to be allocated.
4. Switch the bit of the group from
0
to
1
. In the case of operation via FieldCare this is
done by activating the respective checkbox (see the example below).