Operating menu
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
156
Hauser
"Switch output" submenu
Navigation
Setup → Advanced setup → Switch output
Switch output function
Navigation
Setup → Advanced setup → Switch output → Switch out funct
Description
Select function for switch output.
Selection
• Off
• On
• Diagnostic behavior
• Limit
• Digital Output
Factory setting
Off
Additional information
Meaning of the options
•
Off
The output is always open (non-conductive).
•
On
The output is always closed (conductive).
•
Diagnostic behavior
The output is normally closed and is only opened if a diagnostic event is present. The
Assign diagnostic behavior
parameter (→ 157) determines for which type of event
the output is opened.
•
Limit
The output is normally closed and is only opened if a measured variable exceeds or falls
below a defined limit. The limit values are defined by the following parameters:
–
Assign limit (→ 157)
–
–
•
Digital Output
The switching state of the output tracks the output value of a DI function block. The
function block is selected in the
Assign status
parameter (→ 156).
The
Off
and
On
options can be used to simulate the switch output.
Assign status
Navigation
Setup → Advanced setup → Switch output → Assign status
Prerequisite
Switch output function (→ 156)
=
Digital Output
Description
Select device status for switch output.
Selection
• Off
• Digital output AD 1
• Digital output AD 2
• Digital output 1
Содержание Micropilot FMR56
Страница 197: ......
Страница 198: ...www addresses endress com 71344036 71344036 ...