Installation
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
20
Hauser
6
Installation
6.1
Installation conditions
6.1.1
Mounting position
A
1
2
3
A0016883
• Recommended distance
A
from wall to
outer edge of nozzle: ~ 1/6 of vessel
diameter.
Nevertheless the device should not be
installed closer than 20 cm (7.87 in) to
the vessel wall.
If the wall of the vessel is not smooth
(corrugated metal, welding seams,
irregularities etc.) the distance from the
wall should be kept as large as possible.
If necessary, use an alignment device to
prevent interference reflections from
the wall → 32.
• Not in the center (2), as interference can
cause signal loss.
• Not above the fill stream (3).
• It is recommended to us a weather
protection cover (1) in order to protect
the device from direct sun or rain.
• In extremely dusty applications, the
integrated air purge connection can
prevent clogging of the antenna