Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Operating menu
Hauser
139
"Level" submenu
Navigation
Setup → Advanced setup → Level
Medium type
Navigation
Setup → Advanced setup → Level → Medium type
Description
Specify type of medium.
User interface
• Liquid
• Solid
Factory setting
FMR56, FMR57:
Solid
Additional information
This parameter determines the value of several other parameters and strongly
influences the complete signal evaluation. Therefore, it is strongly recommended
not
to change
the factory setting.
Medium property
Navigation
Setup → Advanced setup → Level → Medium property
Description
Specify relative dielectric constant ε
r
of the medium.
Selection
• Unknown
• DC 1.4 ... 1.6
• DC 1.6 ... 1.9
• DC 1.9 ... 2.5
• DC 2.5 ... 4
• DC 4 ... 7
• DC 7 ... 15
• DC > 15
Factory setting
Dependent on
Medium group
.
Additional information
Dependency on "Medium type" and "Medium group"
Medium group
Medium property
Solid
Unknown
Liquid
Water based (DC >= 4)
DC 4 ... 7
Others
Unknown
For dielectric constants (DC values) of many media commonly used in various
industries refer to:
• the Hauser DC manual (CP01076F)
• the Hauser "DC Values App" (available for Android and iOS)
Содержание Micropilot FMR56
Страница 197: ......