Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Commissioning (block-based operation)
Hauser
81
12
Commissioning (block-based operation)
12.1 Function check
Carry out a post-installation and a post-connection check as per the checklist before
commissioning the device:
• "Post-installation check" checklist → 35
• "Post-connection check" checklist → 41
12.2 Block configuration
12.2.1 Preparatory steps
1. Switch on the device.
2. Note the DEVICE_ID → 61.
3. Open the FOUNDATION Fieldbus configuration program.
4. Load Cff and device description files into the host system or the configuration
program. Make sure you are using the right system files.
5. Identify the device using the
DEVICE_ID
(see Point 2). Assign the desired tag name
to the device by means of the
Pd-tag/FF_PD_TAG
parameter.
12.2.2 Configuring the Resource Block
1. Open the Resource Block.
2. If necessary, disable the lock for device operation.
3. If necessary, change the block name. Factory setting: RS-xxxxxxxxxxx (RB2)
4. If necessary, assign a description to the block by means of the
Tag Description/
TAG_DESC
parameter.
5. If necessary, change other parameters as per the requirements.
12.2.3 Configuring the Transducer Blocks
The measurement and the display module are configured using the Transducer Blocks. The
general procedure is the same for all Transducer Blocks:
1. If necessary, change the block name.
2. Set the block mode to OOS by means of the
Block Mode/MODE_BLK
parameter,
TARGET
element.
3. Configure the level measurement → 84.
4. Set the block mode to
Auto
by means of the
Block Mode/MODE_BLK
parameter,
TARGET
element.
The block mode must be set to
Auto
for the measuring device to function correctly.