Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Electrical connection
Hauser
41
7.
2
1
4
3
A0013837
Connect the cable in accordance with the terminal assignment → 36.
8. When using screened cable: Connect the cable screen to the ground terminal.
9. Screw the cover onto the connection compartment.
10. For instruments with safety pin for the lid: Adjust the safety pin so that its edge is
over the edge of the display lid. Tighten the safety pin.
7.2.1
Pluggable spring-force terminals
Instruments without integrated overvoltage protection have pluggable spring-force
terminals. Rigid conductors or flexible conductors with cable sleeve can directly be inserted
and are contacted automatically.
To remove cables from the terminal: Press on the groove between the terminals using a
flat-tip screwdriver ≤ 3 mm (0.12 inch) while pulling the cables out of the terminals.
mm (in)
≤
3 (0.12)
A0013661
7.3
Post-connection check
m
Are cables or the device undamaged (visual inspection)?
m
Do the cables comply with the requirements?
m
Do the cables have adequate strain relief?
m
Are all cable glands installed, firmly tightened and correctly sealed?
m
Does the supply voltage match the specifications on the transmitter nameplate?
m
Содержание Micropilot FMR56
Страница 197: ......
Страница 198: ...www addresses endress com 71344036 71344036 ...