Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Commissioning (block-based operation)
Hauser
87
12.8 Configuration of the event behavior according to the
FOUNDATION Fieldbus specification FF912
The device complies with the FOUNDATION Fieldbus specification FF912. This has -
among other things - the following consequences:
• The diagnsotic category according to NAMUR recommendation NE107 is transmitted via
the fieldbus in a manufacturer-independent form:
– F: Failure
– C: Function check
– S: Out of specification
– M: Maintenance required
• The diagnostic category of pre-defined groups of events can be adjusted by the user
according to the requirements of the specific application.
• Certain events can be separated from their group and can be handled individually:
– 941: Echo lost
– 942: In safety distance
– 950: Advanced Diagnostic occurred
• Additional information and remedial measures are transmitted together with the event
message via the fieldbus.
The diagnostic messages according to FF912 are available in the host only if the
Multi-bit support
option has been activated in the
FEATURE_SEL
parameter of the
Resource block. For reasons of compatibility, this option is
not
activated on delivery: