Gammapilot M FMG60 PROFIBUS PA
Commissioning
Hauser
67
"Value full" (*14) / "Value empty" (*17)
Range of values
"Calibration start stop" (*15)
Options:
•
stop/edit
This option must be selected if
– the calibration point is not to be entered (e.g. because it has already been entered). The
pulse rate of the calibration point is then displayed in the following function,
"full
calibr." (*16)
or
"empty calibr." (*18)
. If required, this value can be changed.
– the calibration point is to be entered manually. This can be done in the following
function,
"full calibr." (*16)
or
"empty calibr." (*18)
.
•
start
This option is used to start the automatic entering of the calibration point. The
Gammapilot M then changes to the
"avg. pulse rate" (*11)
function.
On-site display
Meaning
value full
*14
These functions are needed for level measurements only.
They are used to specify the level at which the full or empty
calibration are performed.
100%
value empty
*17
0%
optimum value
minimum value
maximum value
Value full (*14)
100%
60%
100%
Value empty (*17)
0%
0%
40%
On-site display
Meaning
calibration
*15
This function is used to start the automatic entering of the
selected calibration point.
stop/edit
start