Commissioning
Gammapilot M FMG60 PROFIBUS PA
60
Hauser
6.3.11 "Output damping" (*0B)
A0018110
1
Level change (or density change)
2
Measured value
Range of values
1 to 999 s
Default
The default depends on the selected
"measuring mode" (*05)
:
• Level: 6 s
• Limit: 6 s
• Density: 60 s
• Concentration: 60 s
Selecting the output damping
The best value of the output damping depends on the process conditions. By enlarging the
output damping, the measured value becomes considerably steadier but also slower.
In order to dampen the influence of strongly fluctuating surfaces or stirrers, it is advisable to
enlarge the output damping. On the other hand, if rapid changes of the measured value have
to be detected accurately, the output damping may not be selected to large.
On-site display
Meaning
Output damping
*0B
This function is used to specify the output damping
(in
seconds) by which changes of the measured value are attenua-
ted.
After a surge in the level or density it takes 5 x
until the new
measured value is reached.
60 s
5 x
t
t
L
1
2