Commissioning
Gammapilot M FMG60 PROFIBUS PA
56
Hauser
6.3.4
"Operating mode" (*04)
NOTICE
The selection can be performed only once and the function is automatically locked after
that. It can only be unlocked again by a reset of the Gammapilot M ("Reset" (*A3)
function).
A0018107
A
One Gammapilot M is sufficient for measuring ranges up to 2 m (6.6 ft ); For larger measuring ranges as many
Gammapilot M as required can be connected (cascading mode). By Software settings they are defined as
B
Master
C
Slave(s) or
D
End-Slave
1
4 to 20 mA HART; PROFIBUS PA; FOUNDATION Fieldbus
Options/display:
•
Stand alone
: This option is selected if the Gammapilot M is used as a single instrument.
•
Master
: This option is selected if the Gammapilot is located at the beginning of a
cascading chain. It receives pulses from a connected slave, adds its own pulses and
calculates the measuring value from this total.
•
Slave
: This option is selected if the Gammapilot M is located in the middle of a cascading
chain. It receives the pulses from an additional connected slave or end-slave, adds its own
pulses and transmits this total to the next device (master or slave). After selecting this
option, the basic setup is finished. When cascading several transmitters the further
calibration is performed on the master only.
•
End slave
: This option is selected if the Gammapilot M is located at the end of a cascading
chain. It does not receive pulses from another device but transmits its own pulses to the
next device (master or slave). After selecting this option, the basic setup is finished. When
cascading several transmitters the further calibration is performed on the master only.
•
Not defined
: Is displayed if no operating mode has been selected yet. In order to continue
the basic setup, a selection is necessary.
NOTICE
If a "Slave" or an "End-slave" are connected to the "FieldCare", the pulse rate of this
device is displayed in the header instead of the measured value.
On-site display
Meaning
Operating mode
*04
This function is used to specify in which operating mode the
Gammapilot M will be used.
Stand alone
Master
Slave
A
B
1
C
D