Gammapilot M FMG60 PROFIBUS PA
Commissioning
Hauser
65
"Avg. pulse rate" (*11)
A0018118
If the value is sufficiently stable, the function can be left by pressing "E".
Thereafter, the Gammapilot M changes to the
"backgr. calib." (*10)
function. Select
"stop/
edit"
to stop the averaging procedure. The value is then automatically transmitted to the
"bgr. pulse rate" (*12)
function.
NOTICE
Bgr. Pulse rate
‣
The maximum integration time is 1000 s. After this time, the value is automatically
transmitted to the
"bgr. pulse rate" (*1B)
function.
‣
The integration is
not
terminated by pressing "E" in the
"avg. pulse rate" (*11)
function.
It is continued until the selection of
"stop/edit"
in the
"backgr. calib." (*10)
function.
This may result in a slight deviation between the last displayed average pulse rate and
the final
"bgr. pulse rate" (*12)
.
"Background pulse rate" (*12)
On-site display
Meaning
Avg. pulse rate
*11
The average pulse rate is displayed in this function (after selec-
tion of "start" in the previous function). Initially, this value fluc-
tuates (because of the decay statistics), but due to the integra-
tion it reaches an average value in the course of time. The
longer the averaging is performed the lower are the remaining
fluctuations.
186 cps
c/s
t
"
E
"
On-site display
Meaning
Backgr. pulse rate
*12
The pulse rate of the background calibration is displayed in this
function. By pressing "E" the displayed value can be confirmed
and the background calibration completed.
"-1"
indicates, that
no background calibration is present yet. In this case there are
two options:
• Either return to the
"background calibration" (*10)
func-
tion and restart the background calibration
• Or enter a known or calculated pulse rate (manual calibra-
tion). Thereafter, the Gammapilot M changes to the
"calibr.
point" (*13)
or
(*1A)
function.
186 cps