Quick start with the Field Communicator
4.3.1
HART security
HART security may be enabled on the 9739 MVD transmitter. To configure the transmitter using HART
protocol, you must disable HART security.
4.3.2
Default values and ranges
Default values and ranges for the most commonly used parameters are provided in Appendix A.
4.4
Configure the primary mA output to report mass flow
rate in a user-selected measurement unit
Note
This procedure assumes that you are starting from the factory-default configuration.
Procedure
1.
Make a connection from the Field Communicator to your transmitter.
2.
Navigate to the On-Line Menu.
3.
Set the measurement unit for mass flow rate.
a.
Press
Configure→Manual Setup→Measurements→Flow→Mass Flow Unit
.
b.
Select the desired measurement unit from the list.
c.
Press the left arrow until you are returned to the Manual Setup menu.
4.
Configure the mA output.
a.
Press
Inputs/Outputs→mA Output 1→Primary Variable
.
b.
Select
Mass Flow Rate
from the list.
c.
Press
ENTER
until you are returned to the mA Output 1 menu.
d.
Press
mA Output Settings
.
e.
Press
PV LRV
and enter an appropriate value for
Lower Range Value
(LRV).
Lower Range Value
specifies the value of
Mass Flow Rate
to be represented by an output level of
0 mA or 4 mA.
f.
Press
ENTER
.
g.
Press
PV URV
and enter an appropriate value for
Upper Range Value
(LRV).
Upper Range Value
specifies the value of
Mass Flow Rate
to be represented by an output level
of 20 mA.
h.
Press
ENTER
.
5.
(Optional) Press
Overview→Shortcuts→Variables→Outputs→Current (mA output 1)
and observe the mA
output reading.
Configuration and Use Manual
53
Содержание Micro Motion 9739 MVD
Страница 6: ......
Страница 8: ......
Страница 30: ...Quick start with the display OFFLINE MAINT RESTORE ZERO RESTORE YES 24 Micro Motion 9739 MVD Transmitters ...
Страница 54: ......
Страница 66: ......
Страница 104: ......
Страница 122: ......
Страница 158: ......
Страница 160: ......
Страница 170: ......
Страница 182: ......
Страница 206: ......
Страница 207: ...Appendices and reference ...
Страница 208: ......
Страница 218: ......
Страница 230: ...Using the transmitter display Figure C 4 Offline menu version information 224 Micro Motion 9739 MVD Transmitters ...
Страница 231: ...Using the transmitter display Figure C 5 Offline menu configuration units and I O Configuration and Use Manual 225 ...
Страница 233: ...Using the transmitter display Figure C 7 Offline menu configuration display Configuration and Use Manual 227 ...
Страница 234: ...Using the transmitter display Figure C 8 Offline menu Simulation loop testing 228 Micro Motion 9739 MVD Transmitters ...
Страница 236: ...Using the transmitter display Figure C 10 Offline menu Zero 230 Micro Motion 9739 MVD Transmitters ...
Страница 239: ...Using ProLink II with the 9739 MVD transmitter Figure D 2 Configuration menu Configuration and Use Manual 233 ...
Страница 241: ...Using ProLink II with the 9739 MVD transmitter Figure D 4 Configuration menu continued Configuration and Use Manual 235 ...
Страница 242: ......
Страница 245: ...Using the Field Communicator with the 9739 MVD transmitter Figure E 2 Overview menu Configuration and Use Manual 239 ...