Integrate the meter with the control system
Note
If
Discrete Output Source
is set to
Fault
and a fault occurs, the discrete output is always ON. The setting of
Discrete Output Fault Action
is ignored.
7.3.4
Configure
Discrete Output Power Source
Display
OFF-LINE MAINT→OFF-LINE CONFG→IO→DO→POWER
ProLink II
ProLink→Configuration→Discrete Output→Power Type
Field Communicator
Configure→Manual Setup→Inputs/Outputs→Discrete Output→Power Source
Use
Discrete Output Power Source
to set the output power source for the discrete output. The power
configuration must match the wiring for the discrete output.
Procedure
Set
Discrete Output Power Source
as desired.
Option
Description
Internal
The output is powered by the transmitter
External
The output is powered by an external power
source.
7.4
Configure the discrete input
Display
OFF-LINE MAINT→OFF-LINE CONFG→IO→DI
ProLink II
ProLink→Configuration→Discrete Input
Field Communicator
Configure→Manual Setup→Inputs/Outputs→Discrete Input
The discrete input is used to initiate one or more transmitter actions from a remote input device.
The discrete input parameters include:
•
Discrete Input Action
•
Discrete Input Polarity
7.4.1
Configure
Discrete Input Action
Display
OFF-LINE MAINT→OFF-LINE CONFG→IO→DI→DI ACT
ProLink II
ProLink→Configuration→Discrete Input→Assignment
Field Communicator
Configure→Alert Setup→Discrete Events→Assign Discrete Action
Discrete Input Action
controls the action or actions that the transmitter will perform when the discrete input
transitions from OFF to ON.
134
Micro Motion 9739 MVD Transmitters
Содержание Micro Motion 9739 MVD
Страница 6: ......
Страница 8: ......
Страница 30: ...Quick start with the display OFFLINE MAINT RESTORE ZERO RESTORE YES 24 Micro Motion 9739 MVD Transmitters ...
Страница 54: ......
Страница 66: ......
Страница 104: ......
Страница 122: ......
Страница 158: ......
Страница 160: ......
Страница 170: ......
Страница 182: ......
Страница 206: ......
Страница 207: ...Appendices and reference ...
Страница 208: ......
Страница 218: ......
Страница 230: ...Using the transmitter display Figure C 4 Offline menu version information 224 Micro Motion 9739 MVD Transmitters ...
Страница 231: ...Using the transmitter display Figure C 5 Offline menu configuration units and I O Configuration and Use Manual 225 ...
Страница 233: ...Using the transmitter display Figure C 7 Offline menu configuration display Configuration and Use Manual 227 ...
Страница 234: ...Using the transmitter display Figure C 8 Offline menu Simulation loop testing 228 Micro Motion 9739 MVD Transmitters ...
Страница 236: ...Using the transmitter display Figure C 10 Offline menu Zero 230 Micro Motion 9739 MVD Transmitters ...
Страница 239: ...Using ProLink II with the 9739 MVD transmitter Figure D 2 Configuration menu Configuration and Use Manual 233 ...
Страница 241: ...Using ProLink II with the 9739 MVD transmitter Figure D 4 Configuration menu continued Configuration and Use Manual 235 ...
Страница 242: ......
Страница 245: ...Using the Field Communicator with the 9739 MVD transmitter Figure E 2 Overview menu Configuration and Use Manual 239 ...