Quick start with ProLink II
4.
Click
Restore Factory Configuration
.
5.
Click
OK
.
3.4
Configure the primary mA output to report mass flow
rate in a user-selected measurement unit
This procedure shows you how to perform these tasks using ProLink II. For all other configuration tasks,
including other options for the mA output, see the configuration sections of this manual.
Note
This procedure assumes that you are starting from the factory-default configuration.
Procedure
1.
Start ProLink II and connect to your transmitter.
2.
Set the measurement unit for mass flow rate.
a.
Choose
ProLink→Configuration
.
b.
In the Configuration window, click the Flow tab.
c.
Select a measurement unit from the
Mass Flow Units
list, then click
Apply
.
3.
Configure the mA output.
a.
In the Configuration window, click the Analog Output tab.
b.
Select
Mass Flow Rate
from the
Primary Variable Is
list.
c.
Enter appropriate values for
Lower Range Value
(LRV) and
Upper Range Value
(URV).
Lower Range Value
specifies the value of
Mass Flow Rate
to be represented by an output level of
0 mA or 4 mA.
Upper Range Value
specifies the value of
Mass Flow Rate
to be represented by
an output level of 20 mA.
4.
Click
OK
to apply the changes and close the Configuration window.
5.
(Optional) Choose
ProLink→Output Levels
and observe the mA output reading.
It should vary between 0 mA or 4 mA and 20 mA according to the mass flow rate of your process.
3.5
Perform a loop test
9739 MVD Transmitter
ProLink→Test→Fix Milliamp 1
ProLink→Test→Fix Milliamp 2
ProLink→Test→Fix Freq Out
ProLink→Test→Fix Discrete Out
ProLink→Test→Read Discrete Input
ProLink→Test→Read Milliamp Input
A loop test is a way to verify that the transmitter and the receiving device are communicating properly. A
loop test also helps you know whether you need to trim mA outputs.
A loop test is a way to verify that the transmitter and the receiving device are communicating properly.
A loop test also helps you know whether you need to trim mA outputs. Performing a loop test is not
Configuration and Use Manual
41
Содержание Micro Motion 9739 MVD
Страница 6: ......
Страница 8: ......
Страница 30: ...Quick start with the display OFFLINE MAINT RESTORE ZERO RESTORE YES 24 Micro Motion 9739 MVD Transmitters ...
Страница 54: ......
Страница 66: ......
Страница 104: ......
Страница 122: ......
Страница 158: ......
Страница 160: ......
Страница 170: ......
Страница 182: ......
Страница 206: ......
Страница 207: ...Appendices and reference ...
Страница 208: ......
Страница 218: ......
Страница 230: ...Using the transmitter display Figure C 4 Offline menu version information 224 Micro Motion 9739 MVD Transmitters ...
Страница 231: ...Using the transmitter display Figure C 5 Offline menu configuration units and I O Configuration and Use Manual 225 ...
Страница 233: ...Using the transmitter display Figure C 7 Offline menu configuration display Configuration and Use Manual 227 ...
Страница 234: ...Using the transmitter display Figure C 8 Offline menu Simulation loop testing 228 Micro Motion 9739 MVD Transmitters ...
Страница 236: ...Using the transmitter display Figure C 10 Offline menu Zero 230 Micro Motion 9739 MVD Transmitters ...
Страница 239: ...Using ProLink II with the 9739 MVD transmitter Figure D 2 Configuration menu Configuration and Use Manual 233 ...
Страница 241: ...Using ProLink II with the 9739 MVD transmitter Figure D 4 Configuration menu continued Configuration and Use Manual 235 ...
Страница 242: ......
Страница 245: ...Using the Field Communicator with the 9739 MVD transmitter Figure E 2 Overview menu Configuration and Use Manual 239 ...