Integrate the meter with the control system
Before assigning actions to an enhanced event or discrete input, check the status of the
event or the remote input device. If it is ON, all assigned actions will be performed when the
new configuration is implemented. If this is not acceptable, wait until an appropriate time to
assign actions to the event or discrete input.
Procedure
Set
Discrete Input Action
as desired.
The default setting is
None
.
Options for
Discrete Input Action
Options for
Discrete Input Action
are shown in Table 7-11 .
Table 7-11
Options for
Discrete Input Action
or
Enhanced Event Action
Label
Action
Display
ProLink II
Field Communicator
None (default)
NONE
None
None
Start sensor zero
START ZERO
Start Sensor Zero
Perform auto zero
Start/stop all totalizers
START STOP
Start/Stop All Totalization
Start/stop totals
Reset mass total
RESET MASS
Reset Mass Total
Reset mass total
Reset volume total
RESET VOL
Reset Volume Total
Reset volume total
Reset gas standard volume
total
RESET GSVT
Reset Gas Std Volume
Total
Reset gas standard volume
total
Reset all totals
RESET ALL
Reset All Totals
Reset totals
Reset temperature-
corrected volume total
TCVOL
Reset API Ref Vol Total
Reset corrected volume
total
Reset CM reference
volume total
RESET STD V
Reset CM Ref Vol Total
N/A
Reset CM net mass total
RESET NET M
Reset CM Net Mass Total
N/A
Reset CM net volume total
RESET NET V
Reset CM Net Vol Total
N/A
Increment CM matrix
INCr CURVE
Increment Current CM
Curve
N/A
Before assigning actions to an enhanced event or discrete input, check the status of the
event or the remote input device. If it is ON, all assigned actions will be performed when the
new configuration is implemented. If this is not acceptable, wait until an appropriate time to
assign actions to the event or discrete input.
7.4.2
Configure
Discrete Input Polarity
Display
OFF-LINE MAINT→OFF-LINE CONFG→IO→DI→DI POLAR
ProLink II
ProLink→Configuration→Discrete Input→DI1 Polarity
Field Communicator
Configure→Manual Setup→Inputs/Outputs→Discrete Input→Polarity
Configuration and Use Manual
135
Содержание Micro Motion 9739 MVD
Страница 6: ......
Страница 8: ......
Страница 30: ...Quick start with the display OFFLINE MAINT RESTORE ZERO RESTORE YES 24 Micro Motion 9739 MVD Transmitters ...
Страница 54: ......
Страница 66: ......
Страница 104: ......
Страница 122: ......
Страница 158: ......
Страница 160: ......
Страница 170: ......
Страница 182: ......
Страница 206: ......
Страница 207: ...Appendices and reference ...
Страница 208: ......
Страница 218: ......
Страница 230: ...Using the transmitter display Figure C 4 Offline menu version information 224 Micro Motion 9739 MVD Transmitters ...
Страница 231: ...Using the transmitter display Figure C 5 Offline menu configuration units and I O Configuration and Use Manual 225 ...
Страница 233: ...Using the transmitter display Figure C 7 Offline menu configuration display Configuration and Use Manual 227 ...
Страница 234: ...Using the transmitter display Figure C 8 Offline menu Simulation loop testing 228 Micro Motion 9739 MVD Transmitters ...
Страница 236: ...Using the transmitter display Figure C 10 Offline menu Zero 230 Micro Motion 9739 MVD Transmitters ...
Страница 239: ...Using ProLink II with the 9739 MVD transmitter Figure D 2 Configuration menu Configuration and Use Manual 233 ...
Страница 241: ...Using ProLink II with the 9739 MVD transmitter Figure D 4 Configuration menu continued Configuration and Use Manual 235 ...
Страница 242: ......
Страница 245: ...Using the Field Communicator with the 9739 MVD transmitter Figure E 2 Overview menu Configuration and Use Manual 239 ...