Integrate the meter with the control system
Procedure
1.
Set
HART Address
to a value between
0
and
15
.
HART Address
must be unique on the network. The default address (0) is typically used unless
you are in a multidrop environment.
Tip
Devices using HART protocol to communicate with the transmitter may use either
HART Address
or
HART Tag
(
Software Tag
) to identify the transmitter. You may configure either or both, as required by
your other HART devices.
2.
Check the setting of
Loop Current Mode
(
mA Output Action
) and change it if required.
Enabled
The primary mA output reports process data as configured.
Disabled
The primary mA output is fixed at 4 mA and does not report process
data.
Tip
Whenever you use ProLink II to set
HART Address
to
0
, ProLink II also enables
Loop Current Mode
.
Whenever you use ProLink II to set
HART Address
to any other value, ProLink II also disables
Loop
Current Mode
. This is designed to make it easier to configure the transmitter for legacy behavior. Be
sure to verify
Loop Current Mode
after setting
HART Address
.
3.
(Optional) Enable and configure
Burst Parameters
.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if another device on the
network requires burst mode communication.
4.
(Optional) Configure
HART Variables
.
Configure
Burst Parameters
Display
N/A
ProLink II
ProLink→Configuration→Device→Burst Setup
Field Communicator
Configure→Manual Setup→Inputs/Outputs→Communications→HART Burst Mode
Burst mode is a specialized mode of communication during which the transmitter regularly broadcasts
HART digital information over the primary mA output. The burst parameters control the information
that is broadcast when burst mode is enabled.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if another device on the network
requires burst mode communication.
Configuration and Use Manual
139
Содержание Micro Motion 9739 MVD
Страница 6: ......
Страница 8: ......
Страница 30: ...Quick start with the display OFFLINE MAINT RESTORE ZERO RESTORE YES 24 Micro Motion 9739 MVD Transmitters ...
Страница 54: ......
Страница 66: ......
Страница 104: ......
Страница 122: ......
Страница 158: ......
Страница 160: ......
Страница 170: ......
Страница 182: ......
Страница 206: ......
Страница 207: ...Appendices and reference ...
Страница 208: ......
Страница 218: ......
Страница 230: ...Using the transmitter display Figure C 4 Offline menu version information 224 Micro Motion 9739 MVD Transmitters ...
Страница 231: ...Using the transmitter display Figure C 5 Offline menu configuration units and I O Configuration and Use Manual 225 ...
Страница 233: ...Using the transmitter display Figure C 7 Offline menu configuration display Configuration and Use Manual 227 ...
Страница 234: ...Using the transmitter display Figure C 8 Offline menu Simulation loop testing 228 Micro Motion 9739 MVD Transmitters ...
Страница 236: ...Using the transmitter display Figure C 10 Offline menu Zero 230 Micro Motion 9739 MVD Transmitters ...
Страница 239: ...Using ProLink II with the 9739 MVD transmitter Figure D 2 Configuration menu Configuration and Use Manual 233 ...
Страница 241: ...Using ProLink II with the 9739 MVD transmitter Figure D 4 Configuration menu continued Configuration and Use Manual 235 ...
Страница 242: ......
Страница 245: ...Using the Field Communicator with the 9739 MVD transmitter Figure E 2 Overview menu Configuration and Use Manual 239 ...