74
MP500/4N-8-16 Programming
5 - SYSTEM COMMISSIONING
This chapter illustrates how to arm and disarm the system totally or partially using the keypads and the electronic and proximity keys.
It also illustrates how to clear alarm indications and how to use the direct function keys (fire, emergency, silent panic).
IMPORTANT!
Users and keys must have been previously acquired, configured and enabled as explained in the applicable
paragraphs of this manual and in the
User Manual
to arm and disarm the system and to clear the alarms.
5.1
ARMING PROCEDURE
The alarm system has various arming modes, some of which are not EN50131 compliant.
EN50131 compliant modes are: arming from keypad, arming with electronic or proximity key, arming by timed programmer or arming
from a specialised input using a mechanical key.
The following modes are not EN50131 compliant: remote arming, arming using GSM and DTMF commands, arming using a remote
control.
The authorisation codes which must be used with keypads are described in paragraph
It is possible to arm the entire system, only some partitions or one or more areas, if the latter are programmed. Areas allow operating
on a subset of partitions at the same time without needing to select them each time.
The user or key must have been assigned to the partition or area during programming in order to operate it.
5.2
ARMING FROM KP500D/N AND KP500DV/N KEYPADS
5.2.1
Total arming (system with partitions only)
Proceed as follows to arm the entire alarm system if no areas are defined:
1) Enter
<Master / User / Installer / Technical Manager code >
and press
.
2) The keypad will beep. Press
to exit without arming. The status LED will light up after 5
seconds (fixed if all partitions are armed, blinking if some partitions are not armed). Press
again if you do not want to wait for 5 seconds.
3) If programmed or if the system is EN50131 grade 3 compliant, the keypad will sound long beeps
initially followed by short beeps for the last 10 seconds.
4) The display will go back to standard view automatically after one minute. Press
to go to
standard display immediately.
IMPORTANT!
The user will arm only the assigned partitions and not necessarily all the partitions even with this procedure.
5.2.2
Total arming (system with areas and partitions)
Proceed as follows to arm the entire alarm system if areas are defined:
1) Enter
<Master / User / Installer / Technical Manager code >
and press
.
2) Enter
or
on the keypad. The procedure will continue as for partitions only if you press
.
If you press
:
3) The keypad will beep. Press
to exit without arming. The status LED will light up after 5 seconds
(fixed if all partitions or areas are armed, blinking if some partitions or areas are not armed) and all
the areas will appear on the display. Press
again if you do not want to wait for 5 seconds.
4) If programmed or if the system is EN50131 compliant, the keypad will sound long beeps initially
followed by short beeps for the last 10 seconds.
5) The display will go back to standard view automatically after one minute. Press
to go to
standard display immediately.
IMPORTANT!
The user will arm only the assigned areas and not necessarily all the areas even with this procedure.
ARM
□□□□••••••••••••
EXECUTED
■■■■••••••••••••
1)AREAS
2)PARTITIONS
ARM
□□••
EXECUTED
■■••
Содержание MP500/16