MP500/4N-8-16 Programming
7.2.16
No Bus communication alarm
This is generated
when...
One or more bus devices are not communicating.
The alarm is generated regardless of partition status (H24).
It activates...
The programmed Tamper outputs.
The dialler to send the respective alarm message (if programmed) in form of numeric code, vocal call or
modem communication.
It is stored...
In the Diagnose Log and in the In the Diagnose Log and in the Tampers memory.
It is indicated...
On the red tampers LED on the keypads.
On the red LED of the readers.
It is stopped by...
Solving the problem.
After having solved the
problem, the control
panel...
Stores end anomaly/tamper in the Diagnose Log.
Activates the dialler to send the respective end of anomaly/tamper alarm message (if programmed) in
form of numeric code, vocal call or modem communication.
Deactivates the programmed Tamper outputs.
7.2.17
Protracted no mains power alarm
This is generated
when...
There is no mains power for a time equal to or higher than the programmed “Lack of power time”.
The alarm is generated regardless of partition status (H24).
It activates...
The programmed "lack of power" outputs.
The dialler to send the respective "lack of power" alarm message (if programmed) in form of numeric
code, vocal call or modem communication.
It is stored...
In the Diagnose Log.
It is indicated...
On The green LED on keypads.
On The red LED on readers.
It is stopped by...
Mains power being restored for at least 5 consecutive minutes.
Five minutes after
mains power is re-
established, the control
panel...
Stores end of no power event in the Diagnose Log.
Activates the dialler to send the respective burglar alarm message (if programmed) in form of numeric
code, vocal call or modem communication.
Deactivates the programmed "lack of power" outputs.
7.2.18
Control panel and other device low battery alarm
This is generated
when...
The battery of the control panel or other devices is recognised as inefficient or missing.
The alarm is generated regardless of partition status (H24).
It activates...
The programmed low battery outputs.
The dialler to send the respective low battery alarm message (if programmed) in form of numeric code,
vocal call or modem communication.
It is stored...
In the Diagnose Log and in the fault and anomaly memory.
It is indicated...
On The yellow failure LED on the keypads.
On The red LED on the readers.
When the battery
charge is restored,
the control panel...
Stores end of low battery event in the Diagnose Log.
Deactivates the programmed low battery outputs.
Activates the dialler to send the respective burglar alarm message (if programmed) in form of numeric
code, vocal call or modem communication.