Electrical Operation and Maintenance Manual for Control Cabinet of EC2-S Industrial Robot
89
Code=4: The target point exceeds the joint motion range. Please reset the position of target point.
Code=5: The movement queue is full. Try it again or the check the controller.
Code=6: The motion axis group is not executed (3). Try it again or the check the controller.
1.2.1.3 Alarm 1802
Fault Description: Emergency stop signal
Fault Reasons: The emergency stop button is pressed.
Solutions: Please check whether the emergency stop button on the teach pendant or the electric cabinet
is released.
1.2.1.4 Alarm 1803
Fault Description: Error in configuration
Fault Reasons: Configuration content is incorrect.
Solutions: Check the content of configuration and reconfigure it.
1.2.1.5 Alarm 1804
Fault Description: Error in I/O module configuration. Please go to the setting interface to modify it,
code_h=%u code_l=%u
Fault Reasons: I/O module configuration is incorrect.
Solutions: Reconfigure in the I/O module configuration interface.
1.2.1.6 Alarm 1805
Fault Description: The overheating alarm of control cabinet
Fault Reasons: There is an alarm that the control cabinet is overheated.
Solutions:
1. Check whether the fan and temperature control switch in the control cabinet work normally;
2. Check whether the temperature control switch value is set correctly.
1.2.1.7 Alarm 1806
Fault Description: Please turn on the servo confirm button on the electric cabinet.
Fault Reasons: The servo confirm button on the electric cabinet is not turned on.
Solutions: Open the electric cabinet to check the servo confirm button, and then turn on it.
1.2.1.8 Alarm 1807
Fault Description: Zone violation alarm
Содержание EC2-S
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 34: ...EFORT INTELLIGENT EQUIPMENT CO LTD 24 15 19 21 front left side panel bottom plate 16 17 20 18...
Страница 84: ...EFORT INTELLIGENT EQUIPMENT CO LTD 74...
Страница 85: ...Electrical Operation and Maintenance Manual for Control Cabinet of EC2 S Industrial Robot 75...
Страница 86: ...EFORT INTELLIGENT EQUIPMENT CO LTD 76...
Страница 87: ...Electrical Operation and Maintenance Manual for Control Cabinet of EC2 S Industrial Robot 77...
Страница 88: ...EFORT INTELLIGENT EQUIPMENT CO LTD 78...
Страница 89: ...Electrical Operation and Maintenance Manual for Control Cabinet of EC2 S Industrial Robot 79...
Страница 90: ...EFORT INTELLIGENT EQUIPMENT CO LTD 80...
Страница 91: ...Electrical Operation and Maintenance Manual for Control Cabinet of EC2 S Industrial Robot 81...
Страница 92: ...EFORT INTELLIGENT EQUIPMENT CO LTD 82...
Страница 120: ......