EFORT INTELLIGENT EQUIPMENT CO.,LTD
62
2
determine the location of the fuse, fuse core, and fuse gear,
FU1 is on the right side of the 24V terminal block in the center of the
control cabinet, and the filter fuse is in the filter of the power interface of
the control cabinet;
3
replace the fuse, fuse core, and fuse gear of the same specification;
4
connect the cables; restore the control cabinet and power on.
Mandatory Measures
When replacing the fuse or fuse gear, please keep the new fuse the same as the
factory specifications, so as to prevent the device from failing to disconnect normally
when there is a short circuit or overcurrent, which may damage other devices!
4.4.6 Replace the Fan
Fig. 4-6 Fan
The following table describes the steps to replace the fan.
Table 4-12 Steps to Replace the Fan
Number
Steps
1
Disconnect the power supply of the control cabinet;
cooling unit 1
cooling unit 2
Содержание EC2-S
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 34: ...EFORT INTELLIGENT EQUIPMENT CO LTD 24 15 19 21 front left side panel bottom plate 16 17 20 18...
Страница 84: ...EFORT INTELLIGENT EQUIPMENT CO LTD 74...
Страница 85: ...Electrical Operation and Maintenance Manual for Control Cabinet of EC2 S Industrial Robot 75...
Страница 86: ...EFORT INTELLIGENT EQUIPMENT CO LTD 76...
Страница 87: ...Electrical Operation and Maintenance Manual for Control Cabinet of EC2 S Industrial Robot 77...
Страница 88: ...EFORT INTELLIGENT EQUIPMENT CO LTD 78...
Страница 89: ...Electrical Operation and Maintenance Manual for Control Cabinet of EC2 S Industrial Robot 79...
Страница 90: ...EFORT INTELLIGENT EQUIPMENT CO LTD 80...
Страница 91: ...Electrical Operation and Maintenance Manual for Control Cabinet of EC2 S Industrial Robot 81...
Страница 92: ...EFORT INTELLIGENT EQUIPMENT CO LTD 82...
Страница 120: ......