Chapter 4 Parameters
4-128
These parameters are used to set the frequencies that are inhibited to operate. This function
can be used to prevent the resonance generated from the original frequency of the machines.
It keeps the drive from running at the resonance frequency of machinery or load system or
other inhibition frequency. There are three frequency areas can be set.
These parameters set the Skip Frequencies. It will cause the AC motor drive never to remain
within these frequency ranges with continuous frequency output. These six parameters should
be set as follows Pr.08.09
Pr.08.10
Pr.08.11
Pr.08.12
Pr.08.13
Pr.08.14. When it is
set to 0.0, the skip frequency is invalid.
The frequency command (F) can be set within the range of skip frequency. At this moment, the
output frequency (H) will be less than the lower limit of skip frequency.
When the drive accelerates/decelerates, the output frequency will pass the range of skip
frequency.
0
08.09
08.10
08.11
08.12
08.13
08.14
Internal
Frequency
Command
Sett ing f requenc y command
frequency is dec reas ed
frequency is increas ed
08.15
Auto Restart After Fault
Settings
0 to 10
Factory Setting: 0
0
Disable
Only after an over-current OC or over-voltage OV fault occurs, the AC motor drive can be
reset/restarted automatically up to 10 times.
Setting this parameter to 0 will disable automatic reset/restart operation after any fault has
occurred.
When enabled, the AC motor drive will restart with speed search, which starts at the frequency
before the fault. To set the waiting time before restart after a fault, please set Pr. 08.07 Base
Block Time for Speed Search.
When the fault times exceeds Pr.08.15 setting, the drive will refuse to restart and the user
needs to press “RESET” for continuous operation.
Related parameter: Pr.08.16 (Auto Reset Time at Restart after Fault)
08.16
Auto Reset Time at Restart after Fault
Unit: second
Settings
0.1 to 6000 sec
Factory Setting: 60.0
This parameter is used to set the auto reset time at restart after fault. After restarting for fault, if
there is no fault for over Pr.08.16 setting from the restart for the previous fault, the auto reset
times for restart after fault will be reset to Pr.08.15 setting..
This parameter should be used in conjunction with Pr.08.15.
For example: If Pr.08.15 is set to 10 and Pr.08.16 is set to 600s (10 min), and if there is no
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...