Chapter 4 Parameters
4-39
Overheat Warning
Applications Purpose
Functions
Related
Parameters
Air conditioner
Safety measure
When AC motor drive overheats, it
uses a thermal sensor to have
overheat warning.
03.00~03.01
04.05~04.08
Two-wire/three-wire
Applications Purpose
Functions
Related
Parameters
General application
To run, stop,
forward and
reverse by external
terminals
VFD-E
MI1:("OPEN":STOP)
("CLOSE":FWD)
MI2:("OPEN": STOP)
("CLOSE": REV)
DCM
FWD/STOP
REV/STOP
VFD-E
MI1:("OPEN":STOP)
("CLOSE":RUN)
MI2:("OPEN": FWD)
("CLOSE": REV)
DCM
RUN/STOP
FWD/REV
3-wire
VFD-E
MI3:("OPEN":STOP)
MI1 ("CLOSE":RUN)
:
MI2:("OPEN": FWD)
("CLOSE": REV)
DCM
STOP
REV/FWD
RUN
02.01
04.04
Operation Command
Applications Purpose
Functions
Related
Parameters
General application
Selecting the
source of control
signal
Selection of AC motor drive control by
external terminals, digital keypad or
RS485.
02.01
04.05~04.08
Frequency Hold
Applications Purpose
Functions
Related
Parameters
General application
Acceleration/
deceleration pause
Hold output frequency during
Acceleration/deceleration
04.05~04.08
Содержание VFD-E Series
Страница 271: ...B 6 B 1 4 DIN Rail Installation...
Страница 304: ...B 39 Driver Installation After connecting IFD6500 to PC please install driver by following steps...
Страница 305: ...B 40 LED Display 1 Steady Green LED ON power is ON 2 Blinking orange LED data is transmitting...
Страница 306: ...B 41 B 9 DIN Rail B 9 1 MKE DRA Unit mm inch SCREW M4 2X 20 22 Kgf cm...
Страница 335: ...D 8 In ladder diagram mode you can perform program editing using the buttons on the function icon row Basic Operation...